Electrical installation – Lenze EMB934x User Manual

Page 107

Advertising
background image

Electrical installation

Installation according to EMC (installation of a CE−typical drive system)

Fuses and cable cross−sections

5

l

107

EDBMB9340 DE/EN/FR 12.0

Shield connection system

ƒ

Use an appropriate clip to connect the shield to the conductive mounting plate of
the control cabinet.

ƒ

The connection should be as close to the cable end as possible.

ƒ

If possible, cover the shield end with a shrink tube.

Remove
lacquer

Large−surface contact
of the cable shield

Shrink tube

Braid

Fig. 5−2

Shield connection

Carefully connect shields, ground connections (GND), and earth potential connections (PE)
to avoid interferences:

ƒ

Do not interrupt shielding.

ƒ

If an interruption cannot be avoided:
– Connect the shields at interruptions (terminal strips, relays, fuses) with a large

surface and both ends to the mounting plate.

ƒ

The cables must be laid as close as possible to the reference potential (dangling
cables are like antennas).

Earthing

Ensure a good equipotential bonding of all system parts (934x regenerative power supply
module, controller, mains filter etc.) by cables to a central earthing point (PE bar). The
minimum cross−sections of the cables must be strictly observed.

Filtering

ƒ

Only use the filters assigned to the regenerative power supply module :
– Mains filters reduce non−permissible high−frequency interferences to permissible

values.