Control connections, Electrical installation, 934x – Lenze EMB934x User Manual

Page 114

Advertising
background image

Electrical installation

Regenerative power supply modules EMB9341 and EMB9342
Control connections

5

l

114

EDBMB9340 DE/EN/FR 12.0

5.3.2

Control connections

Terminal assignment

A1 A2

59

39

22 k

50

mA

50

mA

934x

E1

3

K

10 R

V > 30 V

R

9340vrm007

Fig. 5−6

Digital inputs and outputs

Digital outputs

Terminal

Use

Level with activated output

Data

X2/A1

General fault indication

LOW

LOW level: 0 ... +5 V
HIGH level: +11 ... +30 V
Short−circuit−proof
Output current:
max. 50 mA per output
(external resistance > 480 Ohm
with 24 V)

X2/A2

Mains failure

LOW

)

Note!

Integrate terminal X2/A1 and X2/A2 into the release cascade of the drive
system.

Digital inputs

Terminal

Use

Level with activated input

Data

X2/E1

Inhibit feedback operation

HIGH

LOW level: 0 ... +5 V
HIGH level: +11 ... +30 V
Input current with 24 V: 8mA
Reading and processing of the
input: once per 1 ms (average)

Voltage supply

Terminal

Use

Data

X2/39

Reference potential for terminal 59

DC 24 V, min. 100 mA

X2/59

Connection of the supply voltage for the digital outputs

Screw terminal data

Terminal data

Conductor cross−section

Tightening torque

[mm

2

]

[AWG]

[Nm]

[lb−in]

Flexible

2.5

12

0.5 ... 0.6

4.5 ... 5.3

PZ0

With wire end
ferrule

Advertising