Mechanical installation – Lenze EMB934x User Manual

Page 90

Advertising
background image

Mechanical installation

Regenerative power supply modules EMB9341 and EMB9342
Mains filter mounting

4

l

90

EDBMB9340 DE/EN/FR 12.0

92

365

350

380

15

135

230

7

105

200

PE

L1

L2

L3

LIN E

PE

L1 '

L2 '

L3 '

LO AD

>

100

mm

>

100

mm

9340vrm018

Fig. 4−2

Dimensions of mains filter EZN3A0088H024 for EMB9342

All dimensions in millimetres.

Installation steps

How to mount the mains filter:

1. Drill holes into the mounting plate of the control cabinet for screwing the mains

filter:
– The mains filter must be mounted near the regenerative power supply module

(from a connecting cable length of 30 cm, shielded cables must be used).

– The condition of the wall and the mounting material must provide for the

mechanical connection to be long−lasting.

– Observe dimensions and distances of the drill holes .
– Allow a free space of 100 mm at the top and at the bottom.
– Vertical mounting position with mains connection on the top.

2. Screw the mains filter and the mounting plate of the control cabinet together.

– Provide for long−lasting mechanical connections.