Residual hazards, Safety instructions – Lenze EMB934x User Manual

Page 81

Advertising
background image

Safety instructions

Residual hazards

2

l

81

EDBMB9340 DE/EN/FR 12.0

2.2

Residual hazards

Protection of persons

ƒ

Before working on the regenerative power supply module, check that no voltage is
applied to the power terminals.
– After mains disconnection, the power terminals +UG, −UG remain live for at least

3 minutes.

ƒ

The operating temperature of the heatsink at the regenerative power supply
module is > 70 °C:
– Skin contact with the heatsink results in burns.

ƒ

All pluggable terminals must only be plugged on or removed when no voltage is
applied!

Device protection

ƒ

Cyclic connection and disconnection of the supply voltage can overload and destroy
the input current limitation of the connected regenerative power supply modules:
– Allow at least 3 minutes between disconnection and reconnection!

ƒ

The regenerative power supply module has no overload protection:
– The rated current and maximum current values specified in the technical data

must not be exceeded.

ƒ

If the DC−bus voltage increases during the feedback operation by more than 75 V
(EMB9341/EMB9342) or 100 V (EMB9343) above the rectified value of the mains
voltage, the regenerative power supply module will be overloaded. This may destroy
the device.
– For this reason, the feedback operation must be inhibited if the DC−bus voltage

reaches impermissible values.

– For this purpose please follow the circuit proposals (

124).

2.3

Safety instructions for the installation according to UL/CSA

Warnings!

ƒ

Device is live up to 180 s after mains voltage disconnection.

ƒ

Suitable for use on a circuit capable of delivering not more than 5000 rms
symmetrical amperes, 480 V max, when protected by CC, J, T or R class fuses
(400/480 V devices).

ƒ

Branch circuit protection has to be provided externally in accordance with
corresponding instructions, the National Electrical Code and any additional
codes.

ƒ

Use 60/75 °C or 75 °C copper wire only.

ƒ

Observe the specifications for fuses and screw−tightening torques in these
instructions.

ƒ

Maximum surrounding air temperature 40 °C.

Advertising