Selection of the operating mode

6

l

100

EDK82MV752 DE/EN/FR 7.1

Recommended operating modes for standard applications

The following table helps you to select the appropriate mode of operation for standard
applications:

Application

Operating mode

Single drives

Setting in C0014

recommended

alternatively

With strongly alternating loads

4

2

With a high starting duty

4

2

With speed control (speed feedback)

2

4

With a high dynamic performance (e.g. positioning and infeed drives)

2

With a torque setpoint

5

With torque limitation (power control)

2

4

Three−phase reluctance motors

2

Three−phase sliding rotor motors

2

Three−phase AC motors with a fixedly assigned frequency−voltage
characteristic

2

Pump and fan drives with a square−law load characteristic

3

2 or 4

Group drives
(several motors connected to one controller)

Equal motors and equal loads

2

Different motors and/or alternating loads

2

C0014 = 2: linear V/f characteristic control
C0014 = 3: square−law V/f characteristic control
C0014 = 4: vector control
C0014 = 5: sensorless torque control