Commissioning

Important controller codes

6

l

113

EDK82MV752 DE/EN/FR 7.1

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.

C0517*

v

User menu

l

After mains switching or in the

g

function the code from C0517/1 is
displayed.

l

In the Lenze setting the user menu
contains the most important
codes for commissioning the
operating mode "V/f characteristic
control with a linear
characteristic"

l

If the password protection is
active, only the codes entered in
C0517 can be freely accessed

l

If less than 10 codes are required,
assign the value "0" (zero) to the
memory locations not used. Please
observe that the software
automatically assigns code C0050
to a memory location that is not
used, if it has not been explicitly
assigned to another memory
location.

1 Memory 1

50

C0050

Output frequency (MCTRL1−NOUT)

2 Memory 2

34

C0034

Range of analog setpoint selection

3 Memory 3

7

C0007

Fixed configuration of digital input signals

4 Memory 4

10

C0010

Minimum output frequency

5 Memory 5

11

C0011

Maximum output frequency

6 Memory 6

12

C0012

Acceleration time main setpoint

7 Memory 7

13

C0013

Deceleration time main setpoint

8 Memory 8

15

C0015

V/f rated frequency

9 Memory 9

16

C0016

V

min

boost

10 Memory 10

2

C0002

Parameter set transfer

Possible entries for C0517

xxxx

All codes apart from the codes labelled
with "(A)".

Syntax:
Codes: C0517/x = cccc
Subcodes: C0517/x = cccc.ss

C0608* Fan monitoring

0

0

Inactive

8200 motec 3 ... 7.5 kW:
Function must be activated during
commissioning (recommended:
C0608 = 1)! Otherwise, the controller
may be destroyed due to overheating.
For all other controllers:
It is essential to set C0608 = 0.

1

TRIP error message

2

Warning