Wiring according to emc (ce-typical drive system), Wiring according to emc (ce−typical drive system), Mechanical installation – Lenze E82MVxxx_4Bxxx User Manual

Page 85: Af x1, Kj i

Advertising
background image

Mechanical installation

Wall mounting

Wiring according to EMC (CE−typical drive system)

4

l

85

EDK82MV752 DE/EN/FR 7.1

4.2.4

Wiring according to EMC (CE−typical drive system)

Conditions for trouble−free operation:

ƒ

Except for the mains cable, use shielded cables only.

ƒ

The shield must be carefully connected to PE (see below).

ƒ

Separate control and mains cables from motor cable!

ƒ

Connect motor and mains PE conductors to separate PE terminals.

A

F

X1

82mot398

B

B

C

D

E

F

F

G

X2

H

Shield connection:
1. Prepare the cable

82mot397

K

J

I

2. Insert the cable tie

3. Lay the cable into

the cable tie and
tighten it. The
shield must be
tightly connected
to the shield
sheet.

0

Relay connecting cable

X1

Terminal strip mains connection

1

Mains cables L1, L2, L3, PE (2 cables for loop−through
connection)

X2

Terminal strip motor connection

2

PE connection for mains cables

PES

HF−shield termination by large surface connection to PE

3

Shielded control cables; fix the shield tightly to the
sheet with the cable tie

4

PE connection of motor cable

5

Shielded control cables

6

Motor cable U, V, W (use low−capacitance motor cables!

^ 84)

7

Isolated terminal (e.g. star point for star connected
motor)

8

FIF support

9

Bus−I/O function module in slot 1

:

Fieldbus function module in slot 2