Relay output connection, Electrical installation – Lenze E82MVxxx_4Bxxx User Manual
Page 93
![background image](/manuals/566195/93/background.png)
Electrical installation
Relay output connection
l
93
EDK82MV752 DE/EN/FR 7.1
5.2
Relay output connection
8200mot410
Function
Relay position
Message
(Lenze setting)
Technical data
X1/K11
NC contact
Open
TRIP
AC 250 V/3 A
DC 24 V/2 A ... DC 240 V/0.22 A
X1/K12
Centre contact
X1/K14
NO contact
Closed
TRIP
PES
HF−shield termination by large surface connection to PE
)
Note!
ƒ
Switching of control signals:
– Use shielded cables
– HF−shield termination by PE connection
– The minimum load for switching the signals through correctly is 12 V and
5 mA. Both values have to be exceeded at the same time.
ƒ
Switching of mains potentials:
– Unshielded cables are sufficient
ƒ
For the protection of the relay contacts a corresponding suppressor circuit is
absolutely required for an inductive or a capacitive load!
ƒ
The service life of the relay depends on the type of load (ohmic, inductive or
capacitive) and the value of the switching capacity.
ƒ
The message that is output can be changed in code C0008 or C0415/1.