Mechanical installation

motec with motor or geared motor

Wiring according to EMC (CE−typical drive system)

4

l

81

EDK82MV752 DE/EN/FR 7.1

4.1.1

Wiring according to EMC (CE−typical drive system)

Conditions for trouble−free operation:

ƒ

Except for the mains cable, use shielded cables only.

ƒ

The shield must be carefully connected to PE (see below).

ƒ

Connect motor and mains PE conductors to separate PE terminals.

A

C

X1

E

82mot395

X2

D

B

B

E

E

F

G

Shield connection:
1. Prepare the cable

82mot396

I

H

J

2. Insert the cable tie

3. Lay the cable into

the cable tie and
tighten it. The
shield must be
tightly connected
to the shield
sheet.

0

Connecting cable for

X1

Terminal strip mains connection

l

Relay (for device version 001 or 151) or

X2

Terminal strip motor connection

l

electronic switching output (in case of device versions
152)

PES HF shield connection by large surface connection to PE

1

Mains cables L1, L2, L3, PE (loop through 2 cables to the
mains)

2

PE connection for mains cables

3

Shielded control cables; fix the shield tightly to the sheet
with the cable tie

4

Shielded control cables

5

Isolated terminal (e.g. star point for star connected
motor)

6

PE connection of the motor cable

7

Bus−I/O function module in slot 1

8

Fieldbus function module in slot 2

9

FIF support