Wall mounting
Motor connection

4

l

84

EDK82MV752 DE/EN/FR 7.1

4.2.3

Motor connection

{

Danger!

ƒ

All control terminals only have basic insulation (single isolating distance)
after connecting a PTC thermistor or a thermal contact.

ƒ

Protection against accidental contact in case of a defective isolating
distance is only guaranteed through external measures, e. g. double
insulation.

8200mot468

91

Use low−capacitance motor cables!
(core/core

£ 75 pF/m, core/shield £ 150 pF/m)

The shortest possible motor cables have a positive effect on the drive behaviour!

PES

HF−shield termination by large surface connection to PE

X2/PE2

Do not use the terminal

X2/BR1, X2/BR2

Brake resistor terminals
(For information on operation with brake resistor: see operating instructions)

X2/T1, X2/T2

Terminals of motor temperature monitoring with PTC thermistor (PTC) or thermal
contact
Activate motor temperature monitoring with C0119 (e.g. C0119 = 1)!

Cable cross−sections U, V, W, PE

Type

Cable cross−sections U, V, W, PE

[mm

2

]

[AWG]

E82MV302_4B

1

18

E82MV402_4B

1.5

16

E82MV552_4B

2.5

14

E82MV752_4B

4

12