Commissioning of 8200 motec without function module

l

The 8200 motec can only be used when the FIF cover

0 is mounted! (delivery status).

– If the FIF cover is not mounted, the 8200 motec is inhibited (keypad:

dc).

l

Since the 8200 motec without a function module does not provide any control termi-
nals, starting and stopping during operation is also possible by switching the mains.

l

The

j function saves the setpoint at the time the operation is interrupted when swit-

ching the mains or in case of mains failures. The drive restarts automatically as soon as
the mains recovers!

l

If the drive does not start at step

ƒ (c is not off), press U to enable the 8200 motec.

l

The 8200 motec (device variant with digital switching output K1) without function mo-
dule requires an external DC voltage for the operation of this output.

8200mot146

A

L1 / L2 / L3 / PE

W2

U2

V2

U

PE

1V

1W

1

w

j

y

0....- 50 Hz

z

0....+50 Hz

z
y

w x

v

t

u

s

5000

c

d

j

Hz

0140

3

1

2

AIF

z
y

w

x

v

t

u

s

88888

8888

888

8

a

b

c

d

e

jg

fk

ih

PS



‚m

no

p

q

r

Hi

Hz

%sh

rpm

°C

W

m

A

V

Lo

E82ZBB

E82ZWLxxx

8200mot170

Step

Comment



Connect diagnosis terminal (contains
keypad) with motec. Put the plug of
the connecting cable into the AIF in-
terface on the motec.

Diagnosis terminal and connecting cable are not included in the scope of supply.

‚

Connect mains voltage.
Automatic start is possible!

The controller is ready for operation after approx. 1 second.
Keypad:

dc

ƒ

Select setpoint via the

j function.

Activate

j

g w j

CW rotation

z

c goes off. The drive is running now.
Display indicates output frequency.

CCW rotation

y

Faults during commissioning or operation?

^ chapter 7