Technical data – Lenze E82MVxxx_4Bxxx User Manual

Page 77

Advertising
background image

Technical data

General data and operating conditions

3

l

77

EDK82MV752 DE/EN/FR 7.1

Ambient conditions

Climatic conditions

Storage

IEC/EN 60721−3−1

1K3 (−25 ... +60 °C)

Transport

IEC/EN 60721−3−2

2K3 (−25 ... +70 °C)

Operation

IEC/EN 60721−3−3

3K3 (−20 ... +60 °C)
At temperatures > +40 °C, reduce the rated output current by
2.5 %/°C.

Site altitude

< 4000 m amsl
Reduce rated output current by 5 %/ 1000 m above 1000 m
amsl.

Electrical

Mains connection AC system

Max. mains voltage range

E82MV251... and E82MV371...

1/N/PE or 2/PE 180 V − 0 % ... 264 V + 0 %

E82MV551... to E82MV222...

3/PE 320 V − 0 % ... 550 V + 0 %

E82MV302... to E82MV752...

3/PE 320 V − 0 % ... 550 V + 0 %

Mains frequency

45 Hz − 0 % ... 65 Hz + 0 %

Mechanical

Vibration resistance
(9.81 m/s

2

= 1 g)

Germanischer Lloyd

l

General
conditions

acceleration resistant up to 2 g

Mounting conditions

Mounting position

All mounting positions and mounting alignments are permitted

Free spacess

Above:
To the sides:

100 mm
100 mm

Free spaces with fan
module E82ZMV

for fan exchange:

250 mm

Note regarding the operation with fan module E82ZMV:
The fan module must always be used in the case of

l

motec wall mounting

l

operation without current derating with self−ventilated Lenze motors or Lenze
geared motors

l

operation with non−Lenze motors

Dimensions,

^ Chapter "Mechanical installation"

Weights

^ Chapter "Technical data", "Operation with rated power" or "Operation with
increased rated power"