Electrical installation

Mains connection

5

l

91

EDK82MV752 DE/EN/FR 7.1

5

Electrical installation

5.1

Mains connection

{

Danger!

Dangerous electrical voltage
The discharge current to earth (PE) is > 3.5 mA AC or 10 mA DC.
Possible consequences:

ƒ

Death or severe injuries when touching the device in the event of an error.

Protective measures:

ƒ

Implement the measures required in EN 61800−5−1. Especially:
– Fixed installation
– PE connection must comply with standards (PE conductor diameter

³ 10 mm

2

(Cu) or PE conductor must be connected twice)

8200mot409

93

5.1.1

Fuses and cable cross−sections

Type

Mains

Installation acc. to EN 60204−1

FI

1)

Fuse

Circuit breaker

L1, L2, L3, PE

[mm

2

]

E82MV302_4B
E82MV402_4B
E82MV552_4B
E82MV752_4B

3/PE AC
320 ... 550 V;
45 ... 65 Hz

M16 A
M20 A
M25 A
M32 A

B16 A
B20 A
B25 A
B32 A

2.5
4.0
4.0
6.0

³ 300 mA

E82MV302_4B230
E82MV402_4B230
E82MV552_4B230
E82MV752_4B230

M16 A
M20 A
M25 A
M32 A

B16 A
B20 A
B25 A
B32 A

2.5
4.0
4.0
6.0

³ 30 mA

1)

Universal−current sensitive earth−leakage circuit breaker

Observe all national and regional regulations!