Mechanical installation

Motor mounting
Wiring according to EMC (CE−typical drive system)

4

l

90

EDK82MV752 DE/EN/FR 7.1

4.3.4

Wiring according to EMC (CE−typical drive system)

Conditions for trouble−free operation:

ƒ

Except for the mains cable, use shielded cables only.

ƒ

The shield must be carefully connected to PE (see below).

ƒ

Connect motor and mains PE conductors to separate PE terminals.

A

C

X1

F

82mot39

X2

E

D

B

B

F

F

G

Shield connection:
1. Prepare the cable

82mot39

I

J

H

2. Insert the cable tie

3. Lay the cable into

the cable tie and
tighten it. The
shield must be
tightly connected
to the shield
sheet.

0

Relay connecting cable

X1

Terminal strip mains connection

1

Mains cables L1, L2, L3, PE (loop through 2 cables to the
mains)

X2

Terminal strip motor connection

2

PE connection for mains cables

PES HF−shield termination by large surface connection to PE

3

Shielded control cables; fix the shield tightly to the sheet
with the cable tie

4

PE connection of motor cable

5

Shielded control cables

6

Isolated terminal (e.g. star point for star connected
motor)

7

FIF support

8

Bus−I/O function module in slot 1

9

Fieldbus function module in slot 2