Troubleshooting and fault elimination

Troubleshooting

7

l

114

EDK82MV752 DE/EN/FR 7.1

7

Troubleshooting and fault elimination

7.1

Troubleshooting

Maloperation

Cause

Remedy

Motor does not rotate

DC−bus voltage too low
(red LED is blinking every 0.4 s;
keypad displays: LU)

Check mains voltage

Controller inhibited
(Green LED is blinking, keypad display:

c)

Deactivate controller inhibit, controller
inhibit can be set via several sources

Automatic start inhibited (C0142 = 0 or 2)

LOW−HIGH edge at X3/28
If necessary, correct starting condition
(C0142)

DC−injection braking (DCB) active

Deactivate DC injection brake

Mechanical motor brake is not released

Manual or electrical release of mechanical
motor brake

Quick stop (QSP) active (keypad display:

c)

Deactivate quick stop

Setpoint = 0

Select setpoint

JOG setpoint activated and JOG frequency = 0

Select JOG setpoint (C0037 ... C0039)

Fault active

Eliminate fault

Incorrect parameter set active

Change to correct parameter set via terminal

Operating mode C0014 = −4−, −5− set, but no motor
parameter identification

Identify motor parameters (C0148)

Assignment of several functions excluding each other to
one signal source in C0410

Correct configuration in C0410

Use of internal voltage source X3/20 for the function
modules Standard I/O, INTERBUS, PROFIBUS−DP, or
LECOM−B (RS485):
No jumper between X3/7 and X3/39

Jumper terminals

Motor does not rotate
smoothly

Motor cable defective

Check motor cable

Maximum current set too low (C0022, C0023)

Adjust settings to the application

Motor is under− or overexcited

Check parameter setting (C0015, C0016,
C0014)

C0084, C0087, C0088, C0089, C0090, C0091 and/or
C0092 not adjusted to the motor data

Adjust codes manually or identify motor
parameters (C0148); optimise vector control

Current consumption of
motor too high

Setting of C0016 too high

Correct setting

Setting of C0015 too low

Correct setting

C0084, C0087, C0088, C0089, C0090, C0091 and/or
C0092 not adjusted to the motor data

Adjust codes manually or identify motor
parameters (C0148); optimise vector control

Motor rotates, setpoints
are 0"

A setpoint has been specified by the use of the function

j of the keypad

Set setpoint to "0" with C0140 = 0

Motor parameter
identification stops with
error LP1

Motor is too small in relation to the rated power of the
drive

DC injection brake (DCB) active via terminal

Unacceptable drive
behaviour with vector
control

Various

Optimising the vector control

Torque dip in the field
weakening range
Stalling of the motor
when operating in the
field weakening range

Various