Electrical installation

Mains connection

5

l

92

EDK82MV752 DE/EN/FR 7.1

When using earth−leakage circuit breakers, observe the following:

ƒ

Only install the earth−leakage circuit breaker between supplying mains and drive
controller.

ƒ

Earth−leakage circuit breakers can trip incorrectly due to
– capacitive compensation currents flowing in the cable shields during operation

(particularly with long, shielded motor cables),

– simultaneous connection of several inverters to the mains
– the use of additional interference filters.