Commissioning, Important controller codes – Lenze E82MVxxx_4Bxxx User Manual

Page 111

Advertising
background image

Commissioning

Important controller codes

6

l

111

EDK82MV752 DE/EN/FR 7.1

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.
C0014

v

Operating mode

2

2

V/f characteristic control V ~ f
(linear characteristic with constant V

min

boost)

l

Commissioning is possible without
identifying motor parameters

l

Advantage of identification with
C0148:
– Improved smooth running at

low speeds

– V/f rated frequency (C0015) and

slip (C0021) are calculated and
saved. They do not have to be
entered

3

V/f characteristic control V ~ f

2

(square−law characteristic with constant
V

min

boost)

4

Vector control

In the case of the first selection enter
the motor data and identify them
with C0148
Otherwise commissioning is not
possible
When C0014 = 5, C0019 must be set =
0 (automatic DC injection brake is
deactivated)

5

Sensorless torque control with speed
limitation

l

Torque setpoint via C0412/6

l

Speed limitation via setpoint 1
(NSET1−N1) if C0412/1 is assigned,
otherwise via maximum frequency
(C0011)

C0015

uSEr

V/f rated
frequency

50.00 7.50

{0.02 Hz}

960.00

l

C0015 is calculated and saved
during the motor parameter
identification with C0148.

l

The setting applies to all
permitted mains voltages

C0016

uSEr

V

min

boost

а

0.00

{0.01 %}

40.00

а

device−dependent

Setting applies to all permitted mains
voltages

C0034*

v
uSEr

Range of
setpoint
selection
Standard I/O
(X3/8)

Observe switch position of the
function module!

0

0

Unipolar voltage 0 ... 5 V / 0 ... 10 V
Current 0 ... 20 mA

1

Current 4 ... 20 mA

Reversal of rotation direction only
possible with a digital signal.

2

Bipolar voltage −10 V ... +10 V

l

Minimum output frequency
(C0010) not effective

l

Individually adjust offset and gain

3

Current 4 ... 20 mA open−circuit monitored

TRIP Sd5 if I < 4 mA
Reversal of rotation direction only
possible with a digital signal.

C0034*

v

(A)

uSEr

Range of
setpoint
selection
Application I/O

Observe jumper position of the
function module!

1 X3/1U, X3/1I

0

0

Unipolar voltage 0 ... 5 V / 0 ... 10 V

2 X3/2U, X3/2I

1

Bipolar voltage −10 V ... +10 V

Minimum output frequency (C0010)
not effective

2

Current 0 ... 20 mA

3

Current 4 ... 20 mA

Reversal of rotation direction only
possible with a digital signal.

4

Current 4 ... 20 mA open−circuit monitored

Reversal of rotation direction only
possible with a digital signal.
TRIP Sd5 at I < 4 mA

C0037

JOG1

20.00 −650.00

{0.02 Hz}

650.00 JOG = fixed setpoint

Additional fixed setpoints

ðC0440

C0038

JOG2

30.00 −650.00

{0.02 Hz}

650.00

C0039

JOG3

40.00 −650.00

{0.02 Hz}

650.00

C0050*

uSEr

Output
frequency
(MCTRL1−NOUT)

−650.00

{Hz}

650.00 Read only: Output frequency without

slip compensation

C0087

Rated motor
speed

à

300

{1 rpm}

16000

à

Device−dependent