Electrical installation, Stop – Lenze E82MVxxx_4Bxxx User Manual
Page 94
Electrical installation
Connection of digital switching output (only for device version 152)
l
94
EDK82MV752 DE/EN/FR 7.1
5.3
Connection of digital switching output (only for device version 152)
8200mot411
K14 K12 K11
A
20
X3
7
GND
2
+
_
B
8200 motec
K14 K12 K11
X1
K14 K12 K11
X1
8200 motec
K14 K12 K11
X1
PES
PES
PES
PES
PES
PES
PES
PES
3
Voltage supply via ...
... function module
0
... external DC voltage
1
Terminal Function
Supply
voltage
Circuit state
Ampacity
Supply
voltage
Circuit state
Ampacity
conductive inhibited
conductive inhibited
X1/K12
Switching
output
1)
−
20 V
0 V
10 mA
−
24 V
0 V
50 mA
X1/K14
Supply
voltage
+ 20 V
−
−
−
24 V
(+12 V...+30
V DC)
−
−
−
X1/K11
Earth
1)
the switched output is displayed through "TRIP" (Lenze setting)
(
Stop!
In order to protect the switching output against overvoltages during operation
with inductive loads, a freewheeling diode (e.g. 1N4148) is to be connected in
parallel (see figure below).
X1
K12
K14
K11
24 V DC
+
_
E82MVX1K11K12
The output is short−circuit−proof and protected against inadvertent connection of the
supply voltage potential.
The terminals K11 and K14 are protected against polarity reversal.