Electrical installation

Connection of digital switching output (only for device version 152)

5

l

94

EDK82MV752 DE/EN/FR 7.1

5.3

Connection of digital switching output (only for device version 152)

8200mot411

K14 K12 K11

A

20

X3

7

GND

2

+

_

B

8200 motec

K14 K12 K11

X1

K14 K12 K11

X1

8200 motec

K14 K12 K11

X1

PES

PES

PES

PES

PES

PES

PES

PES

3

Voltage supply via ...

... function module

0

... external DC voltage

1

Terminal Function

Supply
voltage

‚

Circuit state

Ampacity

Supply
voltage

ƒ

Circuit state

Ampacity

conductive inhibited

conductive inhibited

X1/K12

Switching
output

1)

20 V

0 V

10 mA

24 V

0 V

50 mA

X1/K14

Supply
voltage

+ 20 V

24 V
(+12 V...+30
V DC)

X1/K11

Earth

1)

the switched output is displayed through "TRIP" (Lenze setting)

(

Stop!

In order to protect the switching output against overvoltages during operation
with inductive loads, a freewheeling diode (e.g. 1N4148) is to be connected in
parallel (see figure below).

X1

K12

K14

K11

24 V DC

+

_

E82MVX1K11K12

The output is short−circuit−proof and protected against inadvertent connection of the
supply voltage potential.

The terminals K11 and K14 are protected against polarity reversal.