Chapter 8 Configuring Recorders

Configuring the EN50160 Power Quality Recorder

SA300 Substation Automation Unit

105

indication via relay contacts. The event can be found under the STATIC EVENTS

group in the setpoint trigger list.

The power quality fault signal is used for cross triggering multiple recorders through a
dedicated digital input in order to simultaneously record disturbances at different
locations. External triggering of the Waveform and Data recorders for recording

disturbance data is done through a setpoint programmed to monitor the status of a
digital input. For more information on cross triggering, see

Fault Indication and Cross

Triggering

.

EN50160 Harmonics Limits Setup

This setup allows you to adjust compliance limits for harmonic and interharmonic
voltages.

To change the default limits in your device:

1. Select Memory/Log from the Meter Setup menu, and then click on

the EN50160 Harmonics setup tab.

2. Adjust limits you want to change.
3. Download your setup to the device.

The default EM50160 compliance limits are shown in the picture above. You can
change the number of the evaluated harmonics and interharmonics via the

EN50160

Advanced Setup

.

EN50160 Advanced Setup

The EN50160 Advanced Setup allows you to configure the EN50160 evaluation
options in your device.

To configure the EN50160 evaluation options:

1. Select Memory/Log from the Meter Setup menu, and then click on

the EN50160 Advanced Setup tab.

2. Change the EN50160 evaluation options if required.
3. Download your setup to the device.

The default EN50160 evaluation options set in your device are shown in the picture
below.