Chapter 7 Programming the SA300

Using Periodic Timers

SA300 Substation Automation Unit

77

Option Range Default

Description

Counter Setup

Counter Source Setup

Pulse source

None,
DI1-DI48

None

Links a digital input to the counter

Multiplier -10,000

to

10,000

1

The value added to the counter when a

pulse is detected on the pulse source
input

Counter

1-32

1

Defines the target counter for the pulse
source input

Using Periodic Timers

The SA300 has 16 programmable timers that are used for periodic recording and
triggering operations on a time basis through the Control Setpoints. When a pre-

programmed timer interval is expired, the timer generates an internal event that can
trigger any setpoint (see

Using Control Setpoints

). The programmable time interval

can be from 1/2 cycle and up to 24 hours.

To configure the device timers, select General Setup from the Meter Setup menu,

and then click on the Periodic Timers tab.

The available options are described in the following table:

Option Range Default Description

Period

0 = disabled

0.010 - 100,000.000 sec
0.500 - 100,000.000 cycles

0

The timer period

Units Seconds,

Cycles

Seconds

The time units

Seven timers from Timer #10 through Timer #16 are factory preset and cannot be re-
programmed. They are primarily intended for the use with the Power Quality and
Fault recorders. Other timers can be programmed by the user.