Chapter 7 Programming the SA300

Basic Device Setup

SA300 Substation Automation Unit

63

The following table lists available device configuration options.

Option Range

Default

Description

Wiring connection mode
(configuration)

See “Wiring
Connections”
below

4LN3

The wiring connection of the device

V1-V3 PT ratio

1

1.0 - 6500.0

1.0

The phase potential transformer ratio
(primary to secondary ratio)

V1-V3 PT secondary

10-690 V

120

The phase potential transformer’s

secondary phase-to-phase voltage

V4 PT ratio

1

1.0 - 6500.0

1.0

The V4 potential transformer ratio (primary
to secondary ratio)

V4 PT secondary

10-690 V

120

The V4 potential transformer’s secondary

voltage

I1-I3 CT primary current

2

1-10000 A

5

The primary rating of the phase current
transformer on standard (20A/10A) inputs

I1-I3 CT secondary
current

2

1, 5 A

5

The secondary rating of the phase current

transformer on standard (20A/10A) inputs

I4 CT primary current

2

1-10000 A

5

The primary rating of the I4 current
transformer on standard (20A/10A) inputs

I4 CT secondary current

2

1, 5 A

5

The secondary rating of the I4 current
transformer on standard (20A/10A) inputs

I1x-I3x CT primary
current

2

1-10000 A

5

The primary rating of the phase current

transformer on extended (150A) inputs

I1x-I3x CT secondary
current

2

1, 5 A

5

The secondary rating of the phase current
transformer on extended (150A) inputs

I4x CT primary current

2

1-10000 A

5

The primary rating of the I4x current

transformer on extended (150A) inputs

I4x CT secondary current

2

1, 5 A

5

The secondary rating of the I4x current
transformer on extended (150A) inputs

VDC nominal voltage

10-300 V

125

The nominal VDC voltage