Chapter 7 Programming the SA300

Advanced Device Setup

SA300 Substation Automation Unit

65

Option Range

Default

Description

TDD Setup

I Max. Load Current

0 - 10000 A

0

The maximum demand load current for
common current inputs (0 = CT primary)

I4 Max. Load Current 0 - 10000 A

0

The maximum demand load current for I4

(0 = CT primary)

Device Options

Power calculation

mode

S=f(P, Q) (using

reactive power),
Q=f(S, P) (using
non-active power)

S=f(P, Q)

The method used for calculating reactive

and apparent powers (see “Power
Calculation Modes” below)

Energy roll value

10,000 kWh
100,000 kWh
1,000,000 kWh
10,000,000 kWh
100,000,000 kWh
1,000,000,000 kWh

1,000,000,000

The value at which energy counters roll

over to zero

Energy LED pulse

rate, Wh/pulse

0.01-100.00 1.80

Wh/pulse

(one equivalent
disk revolution)

LED pulse constant - the amount of

accumulated energy (in secondary
readings) giving one pulse via “kWh” and
“kvarh” LEDs.

VDC alarm LED
threshold, %

1.0-100.0

85.0%

The VDC threshold in percent of the VDC
nominal voltage. When the measured VDC
voltage drops below this threshold, the
“VDC LOW” alarm LED is lit up. A 5%
hysteresis is provided by default.

Volts Scale, V

10-828 V

828 V

The maximum voltage scale allowed, in
secondary volts. See

Data Scales

in

Appendix E.

Amps Scale, A

1.0-20.0 A

2.0/10.0 A (IEC)
4.0/20.0 A (ANSI)

The maximum current scale allowed, in
secondary amps. See

Data Scales

in

Appendix E.