Chapter 3 Using the RDM

Data Display

28

SA300 Substation Automation Unit

• When direct wiring is used, voltages are displayed in volts with

one decimal place, and power in kilowatts with three decimal
places.

• When wiring via PT is used, the PT ratio up to and including 4.0,

voltages are displayed in volts, and power in whole kilowatts.

• For the PT ratio above 4.0, voltages are displayed in kilovolts,

and power in megawatts with three decimal places.

Currents are displayed in amperes with two decimal places.

Primary and Secondary Volts

Volts are displayed in primary (default) or secondary units. Change the volts display
mode through the Display Setup Menu (see

Configuring the RDM

).

Auto Scroll

With Auto Scroll option enabled (see

Configuring the RDM

), the common

measurements display (main screen)

s

crolls automatically after 30 seconds of

uninterrupted use.

To stop auto scrolling, press either arrow key.

Auto Return to the Main Screen

With Auto Return option enabled (see

Configuring the RDM

), the display

automatically returns to the main screen from any other measurement screen after 30
seconds of uninterrupted use.

Simple Reset of Accumulated Data

When changing data via the communications is not password protected, you can

reset the Min/Max registers, maximum demands and energies from the display mode
without entering the reset menu.

Diagnostics Display

If a critical error occurs in the SA300, the RDM stops updating the display and shows
a diagnostic message “Critic Error”. The diagnostic page in the Status Information

display (see

Status Information Display

below) indicates a critical error until the error

is cleared. See

Device Diagnostic Codes

in Appendix F for the list of diagnostic

events that cause a critical error.

Clear the device diagnostics error via the RDM from the Status Information display
(see

285H

Resetting Device Diagnostics

), or examine what event caused the critical error

and clear the device diagnostics through HyperTerminal (see

286H

Using HyperTerminal

)

or through PAS (see

287H288H

Viewing and Clearing Device Diagnostics

in Chapter 11).

134B

Navigation Keys

The RDM navigation keys are used as follows:

244B

MIN/MAX

MIN/MAX - Selects the Min/Max and Max. Demand Display

245B

THD/TDD

THD/TDD - Selects the Power Quality - Total Harmonics Display

246B

ENERGY

ENERGY - Selects the Energy Display

ENERGY

ENTER

THD/TDD

ESC

S

T

MIN

MAX

diAG

Error

Critic