En50160 harmonics limits setup, En50160 advanced setup, En50160 – SATEC SA300 ezPAC Operation Manual User Manual

Page 106: Advanced setup, Sa300 substation automation unit

Advertising
background image

Chapter 8 Configuring Recorders

Configuring the EN50160 Power Quality Recorder

106

SA300 Substation Automation Unit

The available options are listed in the following table.

Option Range

Default

Description

EN50160 Compliance Statistics

Evaluation

Disabled,
Enabled

Enabled

Enables the EN50160 evaluation

Evaluation

Period

Daily, Weekly Weekly

Defines the EN50160 statistics evaluation period

First Day of the
Week

Sunday-
Saturday

Sunday

Defines the first day of the week for statistics evaluated
on a weekly basis

EN50160 Harmonics Survey

Evaluation

Disabled,

Enabled

Enabled

Enables the harmonics survey log

Evaluation
Period

Daily, Weekly Weekly

Defines the harmonics survey evaluation period

Rapid Voltage Changes

Repetition Rate 1-10

1

Defines the maximum repetition rate in variations per
hour (equal or less than) for rapid voltage changes.
Voltage changes at higher rates are not classified since
they will be subject for flicker.

Flicker

Pst Period

1-10 min

10 min

Defines the period of time for the short-term flicker
evaluation. The standard setting of 10 minutes can be
temporarily changed in the device for testing purposes.

Harmonic Voltage

THD, up to

order

25-50

40

Defines the highest harmonic order included in the THD

evaluation.

Harmonics, up
to order

25-50

25

Defines the highest harmonic order for evaluation of the
harmonic voltages.

Interharmonic Voltage

Evaluation

Disabled,
Enabled

Disabled

Enables the evaluation of the interharmonic voltages

THD, up to

order

25-50

40

Defines the highest interharmonic order included in the

THD evaluation.

Interharmonics,
up to order

25-50

25

Defines the highest harmonic order for evaluation of the
interharmonic voltages.