Configuring the Sequence-of-Events Recorder

86

SA300 Substation Automation Unit

To log setpoint operations, add the “Event log” action to the setpoint actions list. Put

the event log action at the beginning of the list to allow other recorders to use the
sequence number assigned to the event for cross-linking between records logged to
different files. When a setpoint event happens, the Event recorder logs all setpoint
conditions that caused the event and all setpoint actions performed in response to the
event.

Configuring the Sequence-of-Events Recorder

The Sequence-of-Events (SOE) recorder can log four types of events:

Digital input events

Relay output events

Fault events

Setpoint events

Each state transition on a source point (open/closed, start/end) is recorded as a
separate event. Fault events are recorded to the file by default. Others should be
individually enabled to be recorded to the SOE log.

To change the SOE log file size:

1. Select Memory/Log from the Meter Setup menu, and then click

on the Log Memory tab.

2. Double click on the SOE log file partition with the left mouse

button.

3. Select a file type.
4. Select the maximum number of records you want to be

recorded in the file.

5. Click OK, and then send your new setup to the device or save

to the device database.

Linking Digital Inputs to the SOE Log

To link a digital input to the SOE log, check the “SOE Log” box when configuring the

digital input (see

3

Configuring Digital Inputs

). If you linked a digital input to the Fault

recorder, it is automatically connected to the SOE log even if you leaved the “SOE
Log” box unchecked.

Linking Relay Outputs to the SOE Log

To link a relay output to the SOE log, check the “SOE Log” box when configuring the

relay output (see

Programming Relay Outputs

).

Linking Setpoints to the SOE Log

To link a setpoint to the SOE log, add the “SOE Log” action to the setpoint actions list
when configuring the setpoint (see

Using Control Setpoints

).