Chapter 10 Configuring Communication

Configuring DNP3

118

SA300 Substation Automation Unit

when it returns above the threshold plus a predefined

return hysteresis – applicable for AI objects.

Hysteresis for the return threshold is 0.05 Hz for frequency and 2%
of the operating threshold for all other points.

4. Check the “Ev On” box for the points you wish to be included into

event poll reports.

5. In the “Ev Class” box, select the event poll class for the change

event points.

6. Repeat these steps for all points you want to be monitored for

events.

7. Click Send to download your setup to the device.