Appendix B Setpoint Actions

SA300 Substation Automation Unit

159

Appendix B Setpoint Actions

Action Target

Description

NONE

None (no action)

SET EVENT FLAG

1-16

Set user event flag 1-16

CLEAR EVENT FLAG

1-16

Clear user event flag 1-16

OPERATE RELAY

1-32

Operate relay RO1-RO32

RELEASE RELAY

1-32

Release latched relay RO1-RO32

INCREMENT COUNTER 1-32

Increment counter 1-32

DECREMENT COUNTER 1-32

Decrement counter 1-32

CLEAR COUNTER

1-32

Clear counter 1-32

RESET ENERGY

Reset total energy registers

RESET DEMANDS

ALL

Reset all maximum demand registers

RESET DEMANDS

POWER

Reset maximum power demand registers

RESET DEMANDS

VOLT/AMP

Reset maximum volts and ampere demand registers

RESET DEMANDS

VOLT

Reset maximum volt demand registers

RESET DEMANDS

AMP

Reset maximum ampere demand registers

RESET DEMANDS

HRM

Reset maximum harmonic demand registers

RESET TOU ENERGY

Reset summary and TOU energy

RESET TOU DEMANDS

Reset summary and TOU maximum demands

RESET ALL COUNTERS

Clear all counters

CLEAR MIN/MAX LOG

Clear Min/Max log registers

EVENT LOG

OPER

Event log on setpoint operated

EVENT LOG

RELS

Event log on setpoint released

EVENT LOG

ANY

Event log on any setpoint transition

DATA LOG

1-16

Data log 1-16

WAVEFORM LOG

1-8

Waveform Log 1-8

SOE LOG

SOE (Sequence of Events) Log

EXT TRIGGER

1-16

External trigger 1-16 (UDP broadcast trigger message).
See

Cross Triggering Setpoints

.