Chapter 3 Using the RDM

Status Information Display

32

SA300 Substation Automation Unit

The following table shows energy display pages.

Page Label

Parameter

Units

LED

Ac.En.

IP.

1

MWh import

MWh

rE.En.

IP.

2

Mvarh import

Mvarh

AP.En.

3

MVAh MVAh

Ac.En.

EP.

4

MWh export

MWh

rE.En.

EP.

5

Mvarh export

Mvarh

U-h

6

Volt-hours

A-h

7

Ampere-hours

Status Information Display

The RDM has separate status information pages accessible through the MAIN RDM

menu. For information on navigating in the RDM menus, see “Using the Menus”.

To enter the Status Information Display:

1. From the Data display, press SELECT to enter the Main Menu.

The “STA” window flashes.

2. Press ENTER to enter the Status Information Display. Use the

UP/DOWN arrow keys to scroll through the status pages.

To exit the Status Information Display:

1. Press ESC to return to the Main Menu.
2. Press ESC to return to the Data display.

The Status Information Display allows you to view Device Diagnostics, status of
digital inputs and relays, counters and a phase rotation order. It is especially useful
when you connect the SA300 inputs and outputs to external equipment.

The table below lists the status information pages.

Page Parameter

Description

diAG
Critic

1

Error/nonE

When a critical error occurs, the “Critic.
Error” message is displayed (see

Diagnostics Mode

)

rEL.

1.2.3.4.5.6

2

Relay #1-6 status

0 = relay is open, 1 = relay is closed

St.In

1.2.3.4.5.6

3

Digital (status) Inputs #1-#6

0 = open, 1 = closed

St.In

7.8.9.A.b.C

4

Digital (status) Inputs #7-#12

0 = open, 1 = closed