Chapter 2 Device Description

Device Diagnostics

26

SA300 Substation Automation Unit

Device Fault Alarm
The SA300 provides a global "DEVICE FAULT" event flag that is asserted all the time
while one of the non-critical diagnostics events exists. It can be checked from a
setpoint (see

Using Control Setpoints

in Chapter 7) to give a fault indication via a

relay output. If the alarm relay is programmed for failsafe mode using inverting

polarity, then its normally closed contacts will be open if either the device looses
power or a non-critical device fault occurs. Note that in the event of a critical system
failure, all relay outputs are automatically released.

NOTE

The IRIG-B time faults may not be masked and may not be cleared externally. If the
IRIG-B time code signal is not provided, set the device time synchronization input to
any unused digital input (see

Local Settings

in Chapter 7) to avoid fault alarms

caused by the IRIG-B port.