Factory preset periodic data logs, Factory preset fault and pq data logs, Tou profile data log files – SATEC SA300 ezPAC Operation Manual User Manual

Page 89: Sa300 substation automation unit

Advertising
background image

Chapter 8 Configuring Recorders

Configuring the Data Recorder

SA300 Substation Automation Unit

89

Factory Preset Periodic Data Logs

Data logs #1 and #2 are factory preset for periodic recording of the standard power

quantities as shown in the following table.

No. Parameter No.

Parameter

Data Log #1

1

RT (1-cycle) V1

9

RT (1-cycle) Total kVA

2

RT (1-cycle) V2

10

RT (1-cycle) Total PF

3

RT (1-cycle) V3

11

RT (1-cycle) V1 THD

4

RT (1-cycle) I1

12

RT (1-cycle) V2 THD

5

RT (1-cycle) I2

13

RT (1-cycle) V3 THD

6

RT (1-cycle) I3

14

RT (1-cycle) I1 THD

7

RT (1-cycle) Total kW

15

RT (1-cycle) I2 THD

8

RT (1-cycle) Total kvar

16

RT (1-cycle) I3 THD

Data Log #2

1

kW Import Sliding Demand

9

I1 Demand

2

kvar Import Sliding Demand 10

I2 Demand

3

KVA Sliding Demand

11

I3 Demand

4

kWh Import

12

V1 Demand

5

kWh Export

13

V2 Demand

6

kvarh Import

14

V3 Demand

7

kvarh Export

15

RT (1-cycle) I4

8

kVAh

16

RT (1-cycle) V4


Setpoint #1 is preset at the factory to trigger Data logs #1 and #2 in 15 min intervals.

Factory Preset Fault and PQ Data Logs

Data logs #13 and #14 are factory preset for RMS trending on the fault and power

quality events and are intended for the use with the Fault and PQ recorders. The
default PQ and Fault data log configuration is shown in the following table.

No. Parameter No.

Parameter

Data Log #13 (fault data trend)

1

Generic V1

9

Generic V ZERO-SEQ

2

Generic V2

10

Generic VDC

3 Generic

V3

4 Generic

V4

5 Generic

I1x

6 Generic

I2x

7 Generic

I3x

8 Generic

I4x

Data Log #14 (PQ data trend)

1

Generic V1

9

Generic FREQ

2 Generic

V2

3 Generic

V3

4 Generic

V4

5 Generic

I1x

6 Generic

I2x

7 Generic

I3x

8 Generic

I4x


The generic data group represents generic volts, amps, etc., regardless of the data
integration time. The PQ recorder can use different time envelopes to record data

integrated over intervals from a half cycle to 10 minutes depending on the duration of
the power quality event (see

Configuring the Power Quality Recorder

). The Fault

recorder uses only the half-cycle RMS trend.

TOU Profile Data Log Files

Data log files #15 and #16 are configurable to store the TOU monthly profile log and

the TOU daily profile log respectively.

A TOU profile log file is organized as a multi-section file that has a separate section
for each TOU energy and maximum demand register. The number of sections is taken