Chapter 1 Introduction

SA300 Substation Automation Unit

9

EN 50160 Power Quality recorder (special order): onboard power

quality analyzer; programmable limits; EN 50160 power quality event
log, EN 50160 compliance statistics; EN 50160 harmonics survey
statistics; ready-for-use compliance statistics reports; power

frequency, voltage variations, rapid voltage changes, IEC 61000-4-15
flicker, voltage dips, interruptions, temporary overvoltages, transient
overvoltages, voltage unbalance, IEC 61000-4-7 harmonic and
interharmonic voltage, mains signaling voltage.

Event recorder for logging internal diagnostics events, control events

and I/O operations.

Eight Fast Waveform recorders: 57-channel simultaneous recording

with 8 AC, one VDC and 48 digital input channels; optional 41-
channel recording with 8 AC, one VDC, 16 digital and 16 fast analog

input channels; selectable AC sampling rate of 32, 64 or 128 samples
per cycle; 20 pre-fault cycles, 1-ms resolution for digital inputs; up to
3 min of continuous recording with a 4-Mbyte onboard memory at a
rate of 32 samples per cycle; synchronized waveforms from multiple

devices in a single plot

; exporting waveforms in COMTRADE and

PQDIF file formats.

Sixteen Fast Data recorders: 1/2-cycle to 2-hour RMS envelopes; up

to 20 pre-fault and post-fault cycles; programmable data logs on a
periodic basis and on any internal and external trigger; triggering
from the Fault recorder, PQ recorder or control setpoints; exporting
data trends in PQDIF file format.

Embedded Programmable Controller: 32 control setpoints, OR/AND

logic, extensive triggers, programmable thresholds and delays, relay

control, event-driven data recording, cross triggering between
multiple devices via the Ethernet for synchronous event capture and
recording – up to sixteen triggering channels.

High-Class 3-phase Power meter: true RMS, volts, amps, powers,

power factors, unbalance, and neutral current.

Demand Meter: amps, volts, harmonic demands.

Precise Energy and Power Demand Meter: Time-of-Use (TOU), 16

Summary (totalization) and TOU energy and demand registers for
substation energy management; accumulation of energy pulses from
external watt-meters; block and sliding demands; up to 64 energy
sources.

Harmonic Analyzer: up to 63rd harmonic volts and amps; directional

power harmonics and power factor; phasor, symmetrical
components.

32 digital counters for counting pulses from external sources and

internal events.

16 programmable timers from 1/2 cycle to 24 hours for periodic

recording and triggering operations on a time basis.

1-ms satellite-synchronized clock (IRIG-B time-code input).

Backup power supply unit.

5 slots for plug-in I/O modules.

4 Mbyte non-volatile memory with battery backup; optional 64/128-

Mbyte Expansion Memory plug-in module for long-term waveform
and data recording.

AC/DC Inputs

The SA300 is provided with a set of fully isolated AC/DC inputs for connecting to the
AC feeders or station battery:

Advertising