Configuring dnp3, Dnp options, Chapter 10 configuring communication protocols – SATEC SA300 ezPAC Operation Manual User Manual

Page 114: Configuring modbus, Modbus point mapping, Changing raw scales for 16-bit registers

Advertising
background image

Chapter 10 Configuring Communication

Configuring DNP3

114

SA300 Substation Automation Unit

To change the default low and high raw scales:

1. From the Meter Setup menu select Protocol Setup and click on the

Modbus Registers tab.

2. Change the raw scales in the Modbus Options pane. The

allowable range is 0 to 65535.

3. Click Send to download your setup to the device.

Configuring DNP3

DNP Options can be changed both via DNP3 and Modbus. Refer to the SA300 DNP3
Reference guide for information on the protocol implementation and a list of the
available data points.

DNP Options

From the Meter Setup menu select Protocol Setup and click on the DNP Options tab.

The following table describes available DNP options. Refer to the DNP3 Data Object
Library document available from the DNP User’s Group on the DNP3 object types.

Parameter Options Default

Description

Binary Inputs (BI)

Number of BI to

Generate events

0-64

3

21

The total number of BI change event

points for monitoring

Binary Input

Object

Single-bit
With Status

Single-bit

The default BI object variation for

requests with qualifier code 06 when no
specific variation is requested

Binary Input
Change Event
Object

Without Time
With Time

With Time

The default BI change event object
variation for requests with qualifier code
06 when no specific variation is
requested

Analog Inputs (AI)

Number of AI to
Generate events

0-64

3

43

The total number of AI change event
points for monitoring