Programming Analog Outputs

74

SA300 Substation Automation Unit

NOTE:

Always save your AI setup to the site database in order to keep the labels you give
the analog inputs. They are not stored in your device.

Scaling Non-directional Analog Inputs

When programming scales for non-directional analog inputs with a 0-1mA, 0-20mA or
4-20mA current option, provide both zero and full engineering scales. An example is
shown in the picture above for the 0-20 mA analog inputs. Each of the scales

operates independently.

Scaling ±1mA Analog Inputs

When programming engineering scales for directional ±1mA analog inputs, you
should provide only the engineering scale for the +1 mA input current. The
engineering scale for the 0 mA input current is always equal to zero. The device does

not allow you to access this setting. Whenever the direction of the input current is
changed to negative, the device automatically uses your full engineering scale
settings for +1 mA with a negative sign.

Scaling Analog Inputs for 0-2 mA and ±2 mA

The input scales for 0-1 mA and ±1 mA analog inputs are always programmed for
0 mA and +1 mA regardless of the desired input range. If you want to use the entire

input range of 2 mA or ±2 mA, set the analog input scales in your device as follows:

-

0-2 mA: set the 1 mA scale to 1/2 of the required full scale output
for uni-directional parameters, and set the 0 mA scale to the

negative full scale and the 1 mA scale to zero for bi-directional
parameters;

-

±2 mA: set the 1 mA scale to 1/2 of the required full-scale output
for both uni-directional and bi-directional parameters.

For example, to convert voltage readings from the analog transducer that transmits
them in the range of 0 to 2 mA to the range 0 to 120V, set the full range for the +1 mA
analog input to 60V; then the 2 mA reading is scaled to 120V.

Programming Analog Outputs

The SA300 supports up to four expansion Analog Input/Output (AI/AO) modules with

a total of 16 analog outputs. I/O numbers are automatically assigned to the outputs in
the order of connection when the device is powered up.

To configure the analog outputs in your device, select General Setup from the Meter
Setup menu, and then click on the Analog Outputs tab. If you are programming your

device online, Analog outputs that are not present in the device are designated as not
available.

The available AO options are listed in the following table:

Option Format/Range

Description

AO type

0-1mA
±1mA
0-20mA
4-20mA

The AO module type. When connected to the device,
shows the actual AO type read from the AI/AO module.

Output

parameter

Selects the measured parameter to be transmitted

through the analog output channel (see Appendix A)

Zero scale

Defines the low engineering scale (in primary units) for
the analog output corresponding to a lowest (zero)
output current (0 or 4 mA)

Full scale

Defines the high engineering scale (in primary units) for

the analog output corresponding to a highest output
current (1 or 20 mA)