SATEC SA300 ezPAC Operation Manual User Manual

Page 45

Advertising
background image

Chapter 4 Using HyperTerminal

HyperTerminal Commands

SA300 Substation Automation Unit

45

COM1:

Protocol [MODBUS_RTU/MODBUS_ASCII/DNP3]: MODBUS_RTU
New:
Interface [232/422/485]: 232
New:
Device Address [1-247]: 1
New:
Baud Rate [300-115200]: 19200
New:
Data/Parity [7E, 8N, 8E]: 8N
New:
CTS Protocol [y/n]: N
New:
RTS Protocol [y/n]: N
New:
Transmission Delay [0-1000 ms]: 5
New:
Inter-character Timeout [1-1000 ms]: 4
New:

If you want to change a protocol, device address or another port setting, type your
new setting after the “New:” prompt and press Enter. To leave the setting unchanged,

just press Enter.

The following table lists available communication options:

Name Description

Options Default

Protocol

Communications protocol

MODBUS_RTU - Modbus RTU
MODBUS_ASCII - Modbus ASCII
DNP3 - DNP3.0

MODBUS_RTU

Interface

COM1-COM3 interface option

232, 422, 485

232 (COM1)
485 (COM2/3)

Device Address Device address

1-247 (Modbus)
1-255 (DNP3.0)

1

Baud Rate

Baud rate

300-115200 bps

19200 (COM1-

COM4)
57600 (COM5)

Data/Parity

Data format

7E, 8N, 8E

8N

CTS Protocol

When enabled, the port waits for
the CTS signal before sending data

N - disabled
Y - enabled

N

RTS Protocol

When enabled, the RTS signal is
asserted 5 ms before sending data
and during the transmission

N/Y N

Transmission
delay

The minimum time that should
elapse after the last request
character is received to start the
transmission. Increase it if your RS-
485 port or converter fails to switch
the direction of the transmission
fast enough so your application
could lose characters.

0-1000 ms

5

Inter-character

Timeout

The maximum delay for which the

port should wait for a new character
to arrive while the receive line is
inactive. It is used with Modbus
RTU and DNP3.0 protocols to end a
reception of a message.

0-1000 ms

4

The Interface setting need not be changed. All serial ports currently work in half-
duplex mode regardless of the selected interface option.

The modem port (COM5) has a default baud rate of 57600 bps. It is recommended
not to decrease it in order not to affect the port performance.