Chapter 2 Device Description

Controls and Indicators

12

SA300 Substation Automation Unit

Chapter 2 Device Description

Controls and Indicators

Device Controls

The SA300 is entirely controlled either from the remote display module (RDM or
RGM), or by using the supplemental PAS power analysis software package. The unit

has no controls except the PROGRAM-RUN key.

PROGRAM-RUN Key

The PROGRAM-RUN key is used to put the device into program mode for local
servicing and programming. For more information on the Program Mode, see

Opening a Terminal Session

in Chapter 4. For normal operations, the key must be left

in the RUN position.

:

Caution

Do not to put the PROGRAM-RUN key into the RESET position while the device is operating.
This causes immediate restart of the device and possible loss of information or incorrect
operation of the controlled external equipment.

Indicator LEDs

The SA300 has six status indicator LEDs that show present device operation status

and give diagnostics indication; two energy pulsing LEDs that output kWh/kvarh
pulses; and twelve port status LEDs that show present ports status and
communications activity.

LED Name

Color

Status

Description

CPU Yellow

Flashing
1 sec On,
1 sec Off

Device operational and is functioning normally.
The COM1 RS-232 service port is available for
common communications. See

Operational Mode

and

Program Mode

below.

Flashing

2 flashes,
1 sec Off

Device is in the Service Mode and is not

operational. See

Service Mode

below.

Flashing

3 flashes,
1 sec Off

A critical error has occurred - the device is not
operational. Device servicing is required. For more
information, see

Diagnostics Mode

below.

PROGRAM

Red

On

The PROGRAM-RUN key is in PROGRAM position.

The device is either in the Program Mode, or in
the Service Mode if the CPU LED is flashing 3
times.

MEM. BAT.
LOW

Red

On

The memory backup battery is near the end of its
operational life and should be replaced. See the
SA300 Installation Manual for instructions on

replacing the memory battery.

MAIN POWER

Green

On

Voltage is supplied to the main power supply unit.

BACKUP
POWER

Green

On

Voltage is delivered to the backup power supply
unit.

VDC MEAS.

LOW

Red

On

The station battery voltage is below the user-

programmed alarm threshold. For more
information, see

Advanced Device Setup

in

Chapter 7.

kWh/kvarh

Red

Flash at user-
programmed
rate

The device measures imported (consumed) active
and reactive energy. For information on defining
the LED pulse rate, see

Advanced Device Setup

in

Chapter 7.