Chapter 8 Configuring Recorders

Configuring the Event Recorder

SA300 Substation Automation Unit

85

No. File Type

Size,

Bytes

Channels Number of

Records

Number of

Events

Description

1 Event

log

Wrap
around

20000

1000 1000

2

Data log #1

Wrap
around

328320

4320 4320 Configured

for

continuous data
recording

3

Data log #2

Wrap
around

328320

4320 4320 Configured

for

continuous data
recording

10

Data log #9

Wrap
around

42624

12

24 24 Configured

for

EN50160
compliance statistics

11

Data log #10

Wrap

around

15840

3 24 24 Configured

for

EN50160 harmonics
survey

14

Data log #13
(fault data trend)

Wrap
around

224640

4320

4320

Used by the Fault
recorder

15

Data log #14
(PQ data trend)

Wrap
around

288000

6000

6000

Used by the PQ
recorder

24

Waveform log #7 Wrap

around

2136000 10

200

25

Used by the PQ and
Fault recorders

25

Waveform log #8 Wrap

around

683520

8

80

10

Used by the PQ
recorder

26 SOE

log

Wrap
around

14000

1000 1000

27 PQ

log

Wrap
around

64000

2000 2000

28 Fault

log

Wrap
around

40000

1000 1000

Configuring the Event Recorder

To change the Event log file size:

1. Select Memory/Log from the Meter Setup menu, and then click on

the Log Memory tab.

2. Double click on the Event log file partition with the left mouse

button.

3. Select a file type.
4. Select the maximum number of records you want to be recorded in

the file.

5. Click OK, and then send your new setup to the device or save to

the device database.

By default, the Event recorder stores all events related to configuration changes,
reset, and device diagnostics. In addition, it records events related to setpoint
operations. Each setpoint should be individually enabled for recording to the Event

log.