Chapter 7 Programming the SA300

Advanced Device Setup

64

SA300 Substation Automation Unit

Option Range

Default

Description

Nominal frequency

50, 60 Hz

50 (60 for North
America)

The nominal power frequency

Phase order

ABC, ACB

ABC

The normal phase sequence

1

PT Ratio is defined as a relation of the potential transformer’s primary voltage rating to its secondary

rating. For example, if your potential transformer’s primary rating is 14400V and the secondary rating is
120V, then the PT Ratio = 14400/120 = 120.

2

In the SA310 and SA320 models, the settings for the standard current inputs are the same as for the

extended current inputs. When you change setup for one of the current inputs, PAS automatically adjusts
settings for another input.

Wiring Connections

Available wiring modes are listed in the following table:

Wiring Mode

Description

3OP2

3-wire Open Delta using 2 CTs (2 element)

4LN3

4-wire Wye using 3 PTs (3 element), line-to-neutral voltage readings

3DIR2

3-wire Direct Connection using 2 CTs (2 element)

4LL3

4-wire Wye using 3 PTs (3 element), line-to-line voltage readings

3OP3

3-wire Open Delta using 3 CTs (2½ element)

3LN3

4-wire Wye using 2 PTs (2½ element), line-to-neutral voltage readings

3LL3

4-wire Wye using 2 PTs (2½ element), line-to-line voltage readings

3BLN3

3-wire Broken Delta using 2 PTs, 3 CTs (2½-element), line-to-neutral voltage

readings

3BLL3

3-wire Broken Delta using 2 PTs, 3 CTs (2½-element), line-to-line voltage
readings


In 4LN3, 3LN3 and 3BLN3 wiring modes, the voltage readings for min/max volts and
volt demands represent line-to-neutral voltages; otherwise, they will be line-to-line

voltages. The voltage waveforms and harmonics in 4LN3, 3LN3 and 3BLN3 wiring
modes represent line-to-neutral voltages; otherwise, they will show line-to-line
voltages.

Advanced Device Setup

This setup allows you to enable or disable optional calculations and change user-
selectable device options.

To enter the setup dialog, select the device site from the list box on the PAS toolbar,
select General Setup from the Meter Setup menu, and then click on the Advanced
Setup tab.

The following table lists available device options.

Option Range

Default

Description

Demand Setup

Power demand period 1, 2, 5, 10, 15, 20,

30, 60 min

15

The length of the demand period for

power demand calculations

The number of
demand periods in the
sliding window

1-15

1

The number of demand periods to be
averaged for sliding window demands

Power demand sync

source

Meter clock,
DI1-DI48 (digital
inputs 1-48)

Meter clock

The source input for synchronization of

the demand intervals. If a digital input is
specified as the source, a pulse front
denotes the start of the demand interval

Ampere demand
period

0 - 9000 sec

900

The length of the demand period for
ampere demand calculations

Volt demand period

0 - 9000 sec

900

The length of the demand period for volt

demand calculations

Harmonic demand
period

0 - 9000 sec

900

The length of the demand period for
harmonic demand calculations