Chapter 8 Configuring Recorders

Configuring Device Memory

SA300 Substation Automation Unit

83

Chapter 8 Configuring Recorders

The SA300 is provided with a 4MB onboard non-volatile memory for data, event and
waveform recording, that may be extended to 64MB or 128MB with an optional

plug-in memory card.

Before using recorders, the device memory must be partitioned between log files.
The device memory is fully configurable; you can define how much memory to
allocate for each log file. If you want to change the factory settings, follow the
guidelines in the section below.

Configuring Device Memory

The SA300 memory can be partitioned for a total of 28 log files:

Event log

16 Data logs

8 Waveform logs

SOE log

IEEE 1159 or EN 50160 PQ log

Fault log

To view the device memory settings, select Memory/Log from the Meter Setup menu,
and then click on the Log Memory tab.

The following table shows available file options.

Option Format/Range

Description

Type

Wrap around,
Non-wrap

TOU Monthly
Profile
TOU Daily Profile

Defines the file behavior when it is filled up.
Wrap around: recording continues over the oldest

records.
Non-wrap: recording is stopped until the file is cleared.
TOU Monthly Profile: monthly TOU profile data log (only
for data log #15). Wrap around by default.
TOU Daily Profile: daily TOU profile data log (only for

data log #16). Wrap around by default.