Maximum demands, Energy metering, Energy pulses – SATEC SA300 ezPAC Operation Manual User Manual

Page 22: Energy pulse leds, Your device, see, Basic device setup, In chapter 7

Advertising
background image

Chapter 2 Device Description

Metering

22

SA300 Substation Automation Unit

zero at the beginning and up to the final block demand at the end of the demand

interval. If the accumulated demand exceeds the allowed demand at any point, the
final block interval demand is more than the present accumulated demand (or equal if
the load is disconnected).

The predicted demand shows the expected sliding window demand value at the end
of the present demand interval, assuming that the load does not change. The

predicted demand reflects load changes immediately as they happen.

Power demands are calculated for all device energy accumulators, including the
Summary and TOU energy registers (see

Energy Metering

below).

The following table shows demand quantities provided by the device.

Parameter Block

Demand

Sliding

Demand

Accumulated

Demand

Predicted

Demand

Volt demands

×

Ampere demands

×

Voltage THD demand

×

Current THD demand

×

Current TDD demand

×

kW demand (import and export)

Ч

Ч

Ч

Ч

kvar demand (import and export)

Ч

Ч

Ч

Ч

kVA demand

Ч

Ч

Ч

Ч

Summary energy demand (16
configurable registers)

Ч Ч Ч

Maximum Demands

Every demand parameter is provided with the maximum demand register, which
contains a time-stamped peak demand value recorded since the last reset. Maximum
power demand registers are linked to the corresponding sliding demand source
registers. If you wish to use block interval demands instead of sliding window

demands as a source, set the number of the block intervals in the sliding window to 1.

For the TOU demand registers, the device allows automatic recording (profiling) of
the daily and monthly maximum demands to the data log together with the TOU
energy readings.

Energy Metering

The SA300 provides true four-quadrant energy measurements for kWh imported and

exported, kvarh imported and exported, and kVAh, with Class 0.2 ANSI C12-20 or
Class 0.2 IEC 687-1992-6 accuracy. Net and total energy measurements for kWh and
kvarh, and volt-hours and ampere-hours calculations are provided. The standard
measurement range for current inputs (10A IEC or 20A ANSI) is defined when

ordering.

The device provides nine-digit energy counters by default. You can set the counters
to have fewer digits by changing the default energy roll value in your device (see

Advanced Device Setup

in Chapter 7).

Energy Pulses

The SA300 outputs energy pulses through relay contacts with a user-selectable pulse

rate (see

Producing Energy Pulses

and

2

Programming Relay Outputs

in Chapter 7).

The pulse type (complete pulse or KYZ pulse), pulse width and polarity are freely
programmable.

Energy Pulse LEDs

The SA300 has two pulse LEDs on the front that provide energy pulsing for imported

kWh and kvarh.

The LED pulse rate (pulse constant) is user-selectable (see

Advanced Device Setup

in Chapter 7) and is programmed in secondary units. It does not depend on the
ratings of the external transformers. The LED pulse rate is set at the factory to 1.8
Wh/pulse corresponding to one equivalent disk revolution.

Advertising