Chapter 7 Programming the SA300

Generating Energy Pulses

68

SA300 Substation Automation Unit

Daylight Savings Time

The daylight savings time option is enabled in the SA300 by default, and the default

daylight savings time change points are set for the U.S.A. When the daylight savings
time is enabled, the SA300 automatically adjusts the device clock at 02.00 AM when
daylight savings time begins/ends.

If the daylight savings time option is disabled, you need to manually adjust the device
clock for daylight savings time.

Generating Energy Pulses

The SA300 has seven total energy registers where it stores different kinds of
accumulated energies. The SA300 provides internal pulsed events when a
predefined amount of energy is added to the register. These pulses are linkable to the
relay outputs to generate energy pulses for external counters (see

Programming

Relay Outputs

), or to trigger the device control setpoints.

To configure the energy pulses in your device, select the device site from the list box
on the PAS toolbar, select General Setup from the Meter Setup menu, and then click
on the Energy Pulses tab.

The available options are described in the following table:

Option Range

Default

Description

Source accumulator

None
kWh Import
kWh Export
kWh Total
kvarh Import
kvarh Export
kvarh Total
kVAh

None

The source energy register for energy
pulses

kWh/Pulse

1-10,000 kWh Not used The pulse rate - the amount of

accumulated energy per one pulse