Flicker, Method of evaluation, Target values – SATEC SA300 ezPAC Operation Manual User Manual

Page 99: Voltage dips, Statistical results, Indicative values, Voltage interruptions

Advertising
background image

Chapter 8 Configuring Recorders

Configuring the EN50160 Power Quality Recorder

SA300 Substation Automation Unit

99

switching must be carried out to meet supply system or load requirements, it can

reach 10%Un in LV networks, and 6%Un in MV networks.

Flicker

Flicker expresses the visual discomfort caused by repetitive changes of brightness in
lightning subjected to fluctuations of the supply voltage. Flicker is indicated by the
long-term flicker severity parameter Plt, which is evaluated every 2 hours.

Method of Evaluation
The basic flicker measurement is the short-term flicker severity indicator Pst,
evaluated each 10 minutes by instrumentation complying with IEC 61000-4-15. The
indicative long-term flicker severity Plt is evaluated from 12 consecutive Pst values.

For testing purposes, the Pst period can be temporarily changed in the device in the
range of 1 to 10 minutes via the EN50160 Advanced Setup.

Pst values are not classified during intervals when the supply voltage magnitude
exceeds a voltage tolerance limit (

±15% Un) or is affected by voltage dips with depth

more than 15% Un.

Target Values
The flicker compliance limit given in the EN50160 is:

Plt

1 for 95% of a week

The Plt compliance limit can be changed in the device via the EN50160 PQ Recorder
setup.

Voltage Dips

A voltage dip is a sudden reduction of the RMS voltage below 90% of the nominal
value, followed by a return to a value higher than 90% of the nominal in a time

varying from 10 ms to 60 s.

Method of Evaluation
A voltage dip is classified as one polyphase event regardless of the shape and of the

number of phases affected (as per Eurelectric’s Application guide to the European
Standard EN 50160, and IEC 61000-4-30). An event can begin on one phase and
end on another phase. The fault magnitude is recorded separately for each phase
involved. The event duration is measured from the instant at which the voltage falls
below the start threshold on one of the phases to that at which it becomes greater

than the end threshold on all affected phases including a threshold hysteresis.

The basic voltage dip measurement is one-cycle RMS voltage updated each half-
cycle.

The voltage dip threshold can be changed in the device via the EN50160 PQ

Recorder setup.

Statistical Results
The SA300 provides the statistical evaluation of voltage dips using the classification
established by UNIPEDE. Dips are classified by residual voltage magnitude and

duration as shown in Appendix D.

Indicative Values
Under normal operating conditions the expected number of voltage dips in a year

may be from up to a few tens to up to one thousand. The majority of voltage dips
have a duration less than 1 s and a depth less than 60%.

Voltage Interruptions

Voltage interruptions correspond to temporary loss of supply voltage on all phases
lasting less than or equal to 3 minutes in the event of short interruptions, and more

than 3 minutes for long interruptions.

Advertising