Scaling 16-bit ai objects, Configuring dnp3, Dnp options – SATEC SA300 ezPAC Operation Manual User Manual

Page 115: Sa300 substation automation unit

Advertising
background image

Chapter 10 Configuring Communication Protocols

Configuring DNP3

SA300 Substation Automation Unit

115

Parameter Options Default

Description

Analog Input
Object

32-bit
32-bit –Flag
16-bit
16-bit –Flag

16-bit -Flag

The default AI object variation for
requests with qualifier code 06 when no
specific variation is requested

Analog Input

Change Event
Object

32-bit -Time

32-bit +Time
16-bit -Time
16-bit +Time

16-bit +Time The default AI change event object

variation for requests with qualifier code
06 when no specific variation is
requested

Binary Counters (BC)

Number of BC

to Generate
events

0-64

3

0

The total number of BC change event

points for monitoring

Binary Counter
Object

32-bit +Flag
32-bit –Flag
16-bit +Flag
16-bit –Flag

32-bit -Flag

The default BC object variation for
requests with qualifier code 06 when no
specific variation is requested

Binary Counter

Change Event
Object

32-bit -Time

32-bit +Time
16-bit -Time
16-bit +Time

32-bit +Time The default BC change event object

variation for requests with qualifier code
06 when no specific variation is
requested

Frozen Binary
Counter Object

32-bit +Flag
32-bit –Flag
32-bit +Time
16-bit +Flag
16-bit –Flag
16-bit +Time

32-bit -Flag

The default frozen BC object variation
for requests with qualifier code 06 when
no specific variation is requested

DNP General Options

16-bit AI
Scaling

Disabled
Enabled

Enabled

Allows scaling 16-bit analog input
objects (see description below)

16-bit BC
Scaling

x1, x10, x100,
x1000

x1

Allows scaling 16-bit binary counter
objects (see description below)

Re-mapping

Event Points

Disabled
Enabled

Disabled

Allows re-mapping event points starting

with point 0.

SBO Timeout

1

2-30 sec

10

Defines the Select Before Operate
(SBO) timeout when using the Control-
Relay-Output-Block object

Time Sync
Period

2

0-86400 sec

86400

Defines the time interval between

periodic time synchronization requests

Multi Fragment
Interval

50-500 ms

50

Defines the time interval between
fragments of the response message
when it is fragmented

1

The Select Before Operate command causes the device to start a timer. The following Operate
command must be sent before the specified timeout value expires.

2

The device requests time synchronization by bit 4 in the first octet of the internal indication
word being set to 1 when the time interval specified by the Time Sync Period elapses. The
master should synchronize the time in the device by sending the Time and Date object to clear
this bit. The device does not send time synchronization requests if the Time Sync Period is set
to 0.

3

The total number of AI, BI and BC change event points may not exceed 64. When you
change the number of the change event points in the device, all event setpoints are
set to defaults
(see Configuring DNP Event Classes below).

Scaling 16-bit AI objects

Scaling 16-bit AI objects allows accommodating native 32-bit analog input readings to
16-bit object format; otherwise it may cause an over-range error if the full-range value
exceeds a 16-bit point limit.

Scaling is enabled by default. It is not applied to points that are read using 32-bit AI
objects.

Refer to the SA300 DNP3 Reference Guide for information on the data point scales
and on a reverse conversion that should be applied to the received scaled values.