Supplemental Drive Information

Specifications

Unless otherwise noted, the following specifications pertain to drives
equipped with 700 Vector Control or 700S Phase II Control.

Topic

Page

Specifications

A-1

Horsepower/Current Ratings

A-5

Watts Loss

A-6

Fuse and Circuit Breaker Ratings

A-6

Category

Specification

Frame 2

Frames 3A and 3B

Agency
Certification

Listed to UL508C and CAN/CSA-C2.2 No. 14-05. UL Listing for Frame 2 is applicable up to 480V AC. UL Listing for
Frame 3A and 3B is applicable up to 600V AC.

Marked for all applicable European Directives

(1)

EMC Directive (89/336/EEC)

EN 61800-3 Adjustable Speed electrical power drive systems

Low Voltage Directive (73/23/EEC)

EN 50178 Electronic Equipment for use in Power Installations

Certified to AS/NZS, 1997 Group 1, Class A.

These drives are also designed to meet the following specifications:

NFPA 70 - US National Electrical Code
NEMA ICS 3.1 - Safety standards for Construction and Guide for Selection, Installation and Operation of Adjustable Speed Drive

Systems.

IEC 146 - International Electrical Code.
CMAA Specification #70 (Crane Manufacturers of America Association)

(1)

Applied noise impulses may be counted in addition to the standard pulse train causing erroneously high [Pulse Freq] readings.

U

c

US

L

®

N223

Category

Specification

Frame 2

Frames 3A and 3B

Protection 400V

480V

400V

480V

600V

690V

AC Input Overvoltage Trip:

528V AC

528V AC

528V AC

528V AC

760V AC

760V AC

AC Input Undervoltage Trip:

340V AC

340V AC

340V AC

340V AC

340V AC

340V AC

Bus Overvoltage Trip:

815V DC

815V DC

815V DC

815V DC

1168V DC 1168V DC

Bus Undervoltage Shutoff/Fault: 300V DC

300V DC

300V DC

300V DC

300V DC

300V DC

Nominal Bus Voltage:

600V DC

700V DC

600V DC

700V DC

900V DC

1000V DC

Heat Sink Thermistor:

Monitored by microprocessor overtemp trip

Drive Overcurrent Trip

Software Overcurrent Trip:
Hardware Overcurrent Trip:

200% of rated current (typical)
220…300% of rated current (dependent on drive rating)

Line Transients:

Up to 6000 volts peak per IEEE C62.41-1991

Control Logic Noise Immunity:

Showering arc transients up to 1500V peak

Advertising