Cooling Loop Installation

4-9

PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual

Publication 20L-UM001E-EN-P

2. Using a backup wrench on the Complete Drive fitting, tighten the

swivel nut fitting by either of the following two methods:

Hex flats from wrench resistance method (recommended): one (1)

hex flat from wrench resistance.

Torque method: 103…109 N

•m (76…81 lb•ft).

Figure 4.9 Frame 3A and 3B Complete Drive Mating Coolant Connection

Depending on the location of the heat exchanger or chiller relative to the
drive, the following drive cooling loop hose kits are available.

Table 4.A Drive Cooling Loop Hose Kits

DRIVE SIDE

CONNECTION

37° Flare Fitting

Backup Wrench

(use to prevent twisting

during swivel nut tightening)

Do not use Backup Wrench

on fitting locknut

1 5/8" Wrench Flats

Swivel Nut

USER SIDE

CONNECTION

Hose Length

Hoses
in Kit

Drive Side

(1)

Coupling Size

Heat Exchanger Side
Coupling Size

Used With

Hose Kit

(2)

Catalog Number

3 m (10 ft)

2

0.75 inch

0.75 inch

Frame 2

20L-GH10-B1

9.1 m (30 ft)

2

0.75 inch

0.75 inch

Frame 2

20L-GH30-B1

3 m (10 ft)

2

1 inch

1 inch with 90° elbow

Frame 3A

20L-GH10-A2

9.1 m (30 ft)

2

1 inch

1 inch with 90° elbow

Frame 3A

20L-GH30-A2

3 m (10 ft)

2

1 inch

1 inch

Frame 3B

20L-GH10-A1

9.1 m (30 ft)

2

1 inch

1 inch

Frame 3B

20L-GH30-A1

(1)

All drive side hose kit fittings are 37 degree flare.

(2)

Each hose kit contains two (2) hoses and the appropriate connectors.