Liquid-to-Air Heat Exchanger

The liquid-to-air heat exchanger uses radiator technology to transfer heat from a
liquid to surrounding air. This is a simple closed loop system—it does not
require a water supply from the user. However, this system requires surrounding
air that is 5-10 °C below the maximum operating temperature of the drive.

Figure 4.3 Drive and Liquid-to-Air Heat Exchanger Plumbing Arrangement

Figure 4.4

shows a cooling loop diagram for a typical liquid-to-air heat

exchanger.

Figure 4.4 Liquid-to-Air Heat Exchanger Plumbing Diagram

The main components of the liquid-to-air heat exchanger cooling loop are
listed below.

PowerFlex 700L

Drive

Inlet

Drive

Outlet

Hose Kit

= hose or pipe connection

To

Drive

Inlet

Radiator

From

Drive

Outlet

Liquid-to-Air

Heat Exchanger

Flow

Indicator

Ambient

Sensor

Fan

On/Off

Control

TE

Drive Coolant Temp.

TE

Flow Switch

FS

IN

OUT

Level Switch

Radiator

LS

Reservoir

Drive

IN

OUT

Pump

Part Description

Fan

Blows air across the radiator.

Radiator

Transfers heat from liquid to air.

Ambient Sensor

Senses the ambient temperature used for the dew point control.

Drive Coolant Temperature Sensor

Senses the drive coolant temperature used for the dew point control.

Drive Coolant Flow Switch

Measures the drive coolant flow rate.

Level Switch

Senses the level of coolant in the reservoir.

Reservoir

Allows for expansion of coolant.

Pump and Motor

Circulates drive coolant.