Supplemental Drive Information

A-7

PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual

Publication 20L-UM001E-EN-P

Circuit Breakers

The “non-fuse” listings in the following tables include inverse time circuit
breakers, instantaneous trip circuit breakers (motor circuit protectors), and
140M self-protected combination motor controllers. If one of these is
chosen as the desired protection method, the following requirements apply.

• IEC – Both types of circuit breakers and 140M self-protected

combination motor controllers are acceptable for IEC installations.

• UL – Only inverse time circuit breakers and the specified 140M

self-protected combination motor controllers are acceptable for UL
installations.

Table A.F 400 Volt AC Input Protection Devices

Table A.G 480 Volt AC Input Protection Devices

Table A.H 540 Volt DC Input Fusing

Drive
Catalog
Number

Fra

m

e HP (kW) Rating

Input
Rating

Dual Element
Time Delay Fuse

Non-Time Delay
Fuse

Circuit
Breaker

(3)

Motor Circuit
Protector

(5)

ND

HD

Amps

Min.

(1)

Max.

(2)

Min.

Max.

Max.

(4)

Max.

20LC360

2

268 (200)

360

500

750

500

900

900

600

200 (150)

264

400

650

450

900

900

400

(1)

Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.

(2)

Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA.
Ratings shown are maximum.

(3)

Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum

(4)

Maximum allowable rating by US NEC. Exact size must be chosen for each installation.

(5)

Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor FLA. Ratings shown are maximum

Drive
Catalog
Number

Frame

HP (kW) Rating

Input
Rating

Dual Element
Time Delay Fuse

Non-Time Delay
Fuse

Circuit
Breaker

(3)

Motor Circuit
Protector

(5)

ND

HD

Amps

Min.

(1)

Max.

(2)

Min.

Max.

Max.

(4)

Max.

20LD360

2

300 (224)

360

500

750

500

900

900

600

235 (175)

264

400

650

450

900

900

400

(1)

Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.

(2)

Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA.
Ratings shown are maximum.

(3)

Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum

(4)

Maximum allowable rating by US NEC. Exact size must be chosen for each installation.

(5)

Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor FLA. Ratings shown are maximum

Drive
Catalog
Number

Fr

am

e

HP (kW) Rating

DC Input
Rating

Bussmann Fuse

ND

HD

Amps

Amps

Catalog No.

20LC650

3A

500 (370)

365 (270)

1250

(1)

(1)

Only the Dual Inverter for PowerFlex 700L Frame 3A is available as a DC input inverter.

2000

170M6621

(2)

(2)

Two 1000A Bussmann 170M6614 fuses per phase can also be used.

20LC1K2

3B

960 (715)

700 (525)

1250

2000

170M6621

(2)

Advertising