Cooling Loop Installation

4-7

PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual

Publication 20L-UM001E-EN-P

Drive Coolant Connections

Frame 2 Drive or Frame 3A or 3B Power Module

For locations of the coolant inlet and outlet connections on PowerFlex 700L
Frame 2 drives, see

Figure 2.10

. For locations on Frame 3A and 3B Power

Modules, see

Figure 3.20

.

The rated working pressure of the Frame 2 drive is 6.89 bar (100 psi). Size
coolant supply and return lines for 76 LPM (20 gpm) / 6.89 bar (100 psi)
service with a maximum operating temperature of 50 °C (122 °F). The
required operating flow rate and pressure drop is specified in

Table 4.C

.

The rated working pressure of the Frame 3A or 3B Power Module is 12.76
bar (185 psi). Size coolant supply and return lines for 38 LPM (10 gpm) /
12.76 bar (185 psi) service with a maximum operating temperature of 40 °C
(105 °F). The required operating flow rate and pressure drop is specified in

Table 4.C

.

Coolant connections for Frame 2 drives and Frame 3A and 3B Power
Modules are made using 37 degree flare fittings which have a:

• 3/4-inch nominal size

• “-12” SAE dash size

• 1-1/16-12 UN/UNF-2B external thread size

The mating connection is shown in

Figure 4.7

. To make the mating coolant

connection, follow these steps.

1. Assemble the mating version of the fitting (with swivel nut) to each

fluid fitting, and tighten to a wrench resistance of approximately 3.4
N

•m (30 lb•in).

2. Using a backup wrench on the Power Module fitting, tighten the swivel

nut fitting by either of the following two methods:

Hex flats from wrench resistance method (recommended): one and

one-quarter (1-¼) hex flat from wrench resistance.

Torque method: 69…77 N

•m (51…57 lb•ft).

Figure 4.7 Power Module Mating Coolant Connection

37° Flare Fitting

Wrench Flats

Swivel Nut

Backup Wrench

(use to prevent twisting

during swivel nut tightening)