Biocide, Drive cooling loop specifications, Biocide -11 drive cooling loop specifications -11 – Rockwell Automation 20L PowerFlex 700L Liquid-Cooled Adjustable Frequency AC Drive User Manual

Page 99

Advertising
background image

Cooling Loop Installation

4-11

PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual

Publication 20L-UM001E-EN-P

The drive coolant must be compatible with the following materials:

• Copper

• Brass

• Aluminum

• Arimid fiber gasket with nitrile binder (Garlock, Inc. Blue-Gard 3000

®

)

Blue-Gard 3000 is a registered trademark of Garlock, Inc.

• Synthetic rubber hose (Parker Hannifan Corp 801 General Purpose

Hose)

• Viton seal (only Complete Drive)

Biocide

A biocide may be needed to control biological growth. Use of a biocide is
permitted. For specific recommendations, consult a reputable water
treatment company.

Drive Cooling Loop Specifications

* Inhibited ethylene glycol or propylene gylcol must contain a corrosion inhibitor. See

Corrosion Inhibitor on

page 4-10

for an approved source.

Table 4.D

lists the estimated amount of coolant needed for the drive loop

based on the drive frame size. For recommended drive loop coolants, see

Table 4.B

.

Table 4.D Estimated Coolant Amount for the Drive Loop

Table 4.C Coolant Requirements for One Frame 2, 3A or 3B Drive

Drive
Frame Size

Coolant
Temperature Range

Minimum Coolant
Flow Rate

Pressure Drop

(2)

From Drive Inlet to Drive

Outlet at Minimum Coolant Flow Rate

Coolant Type

2

0…50 °C (32…122 °F)

30.3 LPM (8 gpm)

1.58 bar (23 psi)

WEG50

(3)

or

WPG50

(4)

3A

0…40 °C (32…104 °F)

30.3 LPM (8 gpm)

0.35 bar (5 psi)

3B

0…40 °C (32…104 °F)

56.8 LPM (15 gpm)

(1)

0.48 bar (7 psi)

(1)

(1)

Frame 3B includes separate converter and inverter power modules. A single inverter or converter power module requires a minimum flow rate of 30.3
LPM (8 gpm) at 0.35 bar (5 psi).

(2)

Pressure drop does not include any system connections such as hoses or piping. Cooling systems must be sized to provide minimum flow
considering entire system pressure drop.

(3)

WEG50 equals good quality or distilled water with approved, inhibited* ethylene glycol, 50% glycol by volume.

(4)

WPG50 equals good quality or distilled water with approved, inhibited* propylene glycol, 50% glycol by volume.

Drive Size

Estimated Amount of Coolant

(1)

(1)

The estimated amount of coolant is based on the heat exchanger
using 1.2 m (4 ft) hoses. Longer hoses require more coolant. The
maximum hose length of 9.1 m (30 ft) would require up to an
additional 2.8 liters (3/4 gal).

Frame 2

15.1 liters (4 gal)

Frame 3A

19 liters (5 gal)

Frame 3B

19 liters (5 gal)