Rockwell Automation 20L PowerFlex 700L Liquid-Cooled Adjustable Frequency AC Drive User Manual

Page 119

Advertising
background image

Supplemental Drive Information

A-3

PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual

Publication 20L-UM001E-EN-P

Control

(continued)

Frequency Control
(Vector Control only):

Speed Regulation - w/Slip Compensation (Volts per Hertz Mode)

0.5% of base speed across 40:1 speed range
40:1 operating range
10 rad/sec bandwidth

Speed Regulation - w/Slip Compensation (Sensorless Vector Mode)

0.5% of base speed across 80:1 speed range
80:1 operating range
20 rad/sec bandwidth

Speed Control

Vector Control:

Speed Regulation - without feedback (Vector Control Mode)

0.1% of base speed across 120:1 speed range
120:1 operating range
50 rad/sec bandwidth

Speed Regulation - with feedback (Vector Control Mode)

0.001% of base speed across 120:1 speed range
1000:1 operating range
250 rad/sec bandwidth

700S Phase II Control:

Speed Regulation - without feedback

0.1% of base speed across 120:1 speed range
120:1 operating range
50 rad/sec bandwidth

Speed Regulation - with feedback

0.001% of base speed across 120:1 speed range
1000:1 operating range
740 rad/sec bandwidth

Torque Regulation

Vector Control:

Torque regulation without Feedback; ±

5%, 600 rad/sec bandwidth

Torque regulation with Feedback; ±

2%, 2500 rad/sec bandwidth

700S Phase II Control:

Torque regulation without Feedback; ±

10%, 600 rad/sec bandwidth

Torque regulation with Feedback; ±

5%, 4400 rad/sec bandwidth

Selectable Motor Control

Vector Control:

Sensorless Vector with full tuning. Standard V/Hz with full custom capability and Vector Control
with Force Technology (with and without feedback).

700S Phase II Control:

Vector Control with Force Technology (with and without feedback), V/Hz Control, and permanent
magnet motor control.

Stop Modes

Vector Control:

Multiple programmable stop modes including Ramp, Coast, DC-Brake, Ramp-to-Hold, and
S-curve.

700S Ph. II Control:

Multiple programmable stop modes including Ramp, Coast, and Current Limit.

Accel/Decel

Vector Control:

Two independently programmable accel and decel times. Each time may be programmed from
0…3600 seconds in 0.1 second increments.

700S Phase II Control:

Independently programmable accel and decel times, adjustable from 0…6553.5 seconds in 0.01
second increments.

Intermittent Overload:

110% Overload capability for up to 1 minute 150% Overload capability for up to 3 seconds

Current Limit Capability

Vector Control:

Proactive Current Limit programmable from 20 to 160% of rated output current. Independently
programmable proportional and integral gain.

700S Phase II Control:

Independent Motoring and Regenerative Power Limits programmable to 800% of rated output
current.

Electronic Motor Overload
Protection:

Class 10 motor overload protection according to NEC article 430 and motor over-temperature
protection according to NEC article 430.126 (A)(2). UL File E59272.

Category

Specification

Frame 2

Frames 3A and 3B

Advertising