3-34

Frame 3A and 3B Installation

PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual
Publication 20L-UM001E-EN-P

Synchronization
Connections for Frame 3A

Coupled Power Modules

Frame 3A combined Converter/Inverter Power Modules are configured only
as coupled power modules. Coupling the Converter and Inverter is achieved
by using two factory-installed cables: a control synchronization cable and
an inverter-to-converter DPI communication cable. The two cables are
described in the next two subsections.

Control Synchronization Cable

To enable synchronization between the Inverter control board and the
Converter control board, a factory-installed control synchronization cable
connects each board. No user connection is required. However, the
connection method is different for PowerFlex 700L drives with 700 Vector
Control than for 700S Phase II Control. The 700 Vector Control
synchronization cable connection is shown in

Figure 3.31

. The 700S Phase

II Control synchronization cable connection is shown in

Figure 3.32

.

Figure 3.31 Frame 3A 700 Vector Control Synchronization Cable Connection

TB2 Header on

700 Vector

Control Cassette

P1 Terminal Block

on Active Converter

Control Cassette

TB2-2

TB2-1

P1-7

1

P1-8

15

SHLD

SHLD

24 VDC

DC POSITIVE

DC NEGATIVE

1 120 VAC

2 PRECHARGE COIL

6 INDUCTOR OVERTEMP

WIRE RANGE:
24-10 AWG
(0.2-4 MM)

4 CHARGE FEEDBACK

GATE ENABLE

STRIP LENGTH:
0.31 IN (8 MM)
TORQUE:
8 IN-LB
(0.9 N-M)

Control Synchronization

Cable (Factory-Installed)